Back
IEC/EN 60898-1

Coordinating MCB rated current and selectivity in a board

Selectivity is right when a fault clears only the affected circuit, not half the board. This guide shows how to coordinate rated current, tripping curve and breaking capacity across several miniature circuit breakers to IEC/EN 60898-1.

5 minStand: 2026-07Geprüft: Technical editors
View circuit breakers
B/C/D
tripping curves
1.6:1
rule of thumb rating step
6-10 kA
typical breaking capacity Icn
60898-1
governing standard
Inhalt
  1. Basics
  2. Curves B/C/D
  3. Grading and discrimination
  4. Frequently asked questions

What do rated current and selectivity mean?

The rated current In is the continuous current an MCB can carry without tripping. It is matched to the conductor cross-section and its permissible loading, not to the load alone. Selectivity (discrimination) means that on a fault only the breaker immediately upstream of the fault trips, while the device above it stays closed.

In a graded distribution board several protective devices sit in series: the main switch or upstream fuse, then group or sub-distribution boards, and at the bottom the final circuit. Without coordinated grading a short circuit in one socket could shut down the entire board.

Selectivity is assessed on two levels: in the overload region through graded rated currents, and in the short-circuit region through current or time discrimination. Both must be correct for the installation to react selectively under fault.
Board planning

How to plan the layout and protection of a distribution board from scratch.

Read the guide

Which tripping curve fits the load?

The tripping curve defines at what multiple of the rated current the instantaneous magnetic release operates. To IEC/EN 60898‑1 the usual types are B, C and D. The right choice prevents nuisance tripping on energising while still ensuring fast clearance on a short circuit.

  • Type B: lowest inrush margin, trips early - ideal for resistive loads and shock protection on long runs.
  • Type C: the standard for mixed loads with moderate inrush currents.
  • Type D: for loads with high momentary starting currents so the breaker does not trip needlessly.
  • Always verify that the disconnection condition to IEC 60364‑4‑41 is still met at the end of the line.
The higher the curve (D rather than B), the larger the short-circuit current at the line end must be for the magnetic release to operate within the required time. Long cable runs may force the choice back to B or C.

How do you grade rated currents selectively?

In the overload region a common rule of thumb is a step ratio of about 1.6:1 between the upstream and downstream rated current - for example 63 A over 40 A or 40 A over 25 A. This keeps the upstream breaker thermally stable while the downstream one reacts first.

In the short-circuit region rated-current grading alone is often not enough. Here you rely on current discrimination (the upstream breaker does not reach its magnetic threshold at the fault current present) or on time discrimination using selective main circuit breakers or moulded-case breakers with an adjustable short-time delay.

The actual selectivity limit is stated in the manufacturer discrimination tables. For each breaker pairing they give the maximum fault current up to which selectivity is guaranteed - a rule of thumb does not replace these tables.
  • The breaking capacity Icn of the upstream device must cover the maximum prospective short-circuit current at the location (typically 6 kA residential, 10 kA and above commercial).
  • Downstream breakers must not exceed their back-up protection limit provided by the upstream fuse.
  • Always check selectivity pairwise against the manufacturer table, never assume it globally.

Frequently asked questions

What determines the rated current of an MCB?

The current-carrying capacity of the protected cable and its installation method, not the load alone. The rated current must sit below the permissible continuous loading of the conductor cross-section.

Is grading rated currents enough for selectivity?

Only in the overload region. The short-circuit region additionally needs current or time discrimination, proven via the manufacturer tables and the tripping curve.

What does the 1.6:1 rule of thumb mean?

A factor of about 1.6 should sit between the upstream and downstream rated current so the upstream breaker does not trip before the downstream one under overload.

What is the difference between curves B, C and D?

They set the multiple of rated current at which the instantaneous magnetic release operates: B at 3‑5x, C at 5‑10x, D at 10‑20x. D is intended for high inrush currents.

Need a selectively protected board?

We supply MCBs in B, C and D curves with the right breaking capacity plus selective main circuit breakers - tested to IEC/EN 60898-1.

Standard tested

Breakers to IEC/EN 60898-1 with documented Icn.

Full range

B, C and D curves for every load type.

Discrimination proven

Design based on verified manufacturer tables.

Expert advice

Our specialists help you grade the protection.

More guides