Back
IEC 60364-4-41

RCD 30 mA or 300 mA - which rated current fits?

The rated residual current IΔn defines what a residual current device actually protects. This guide explains why 30 mA covers personal protection and 300 mA covers fire protection, which standards apply and how to combine both values correctly.

5 minStand: 2026-07Geprüft: Technical editors
View residual current devices
30 mA
personal protection IΔn
300 mA
fire protection IΔn
≤ 30 mA
safe for the heart
60364-4-41
governing standard
Inhalt
  1. IΔn basics
  2. 30 mA for people
  3. 300 mA for fire
  4. Selective grading
  5. Frequently asked questions

What does the rated residual current IΔn mean?

The rated residual current IΔn is the fault current at which an RCD (residual current device) reliably trips. It is printed on the device and defines its purpose: small values such as 30 mA protect people, larger values such as 300 mA protect against fire in the wiring.

An RCD constantly measures the sum of all currents flowing in and out. During normal operation this sum is zero. If current leaks away through a fault, for example through the human body or damaged insulation to earth, a difference appears. Once it exceeds IΔn, the RCD disconnects the circuit within milliseconds.

By standard an RCD may trip anywhere between half and the full rated value. A 30 mA RCD can therefore trip from around 15 mA, and a 300 mA device from around 150 mA.
  • IΔn 10 mA: enhanced protection in special areas such as medical rooms.
  • IΔn 30 mA: standard personal protection for sockets and final circuits.
  • IΔn 100 mA / 300 mA: fire and system protection for whole circuit groups.
  • IΔn 500 mA and above: pure system protection with no personal protection.

Why do 30 mA protect people?

The value 30 mA is derived from the physiological effect of current on the body. Currents above roughly 30 mA can trigger ventricular fibrillation if they persist. An RCD with IΔn 30 mA disconnects so quickly that a dangerous current through the body never has time to build up.

According to IEC 60364‑4‑41 (and the national DIN VDE 0100‑410), additional protection by an RCD with IΔn ≤ 30 mA is mandatory for socket outlets up to 32 A used by ordinary persons and for final circuits outdoors. The 30 mA RCD thus delivers classic personal protection: it prevents electric shock from direct or indirect contact.

A 30 mA RCD typically trips within 300 ms at the rated value and much faster at multiples of it. This short time keeps the energy passing through the body below the hazard threshold.

What are 300 mA used for?

An RCD with IΔn 300 mA does not protect people, it prevents fires caused by insulation faults. If a small fault current leaks continuously to earth through damaged wiring, the resulting heat can ignite insulation material. Fault currents of only a few hundred milliamperes are enough to start a smouldering fire at the fault location.

The 300 mA RCD trips before the fault current can build up this critical heat over time. It is therefore often used upstream for whole distribution boards, for timber constructions, agricultural buildings or fire-risk premises per IEC 60364‑4‑42. For fire protection, RCDs with IΔn ≤ 300 mA are specified.

300 mA is too high for personal protection: at this value a dangerous body current could already flow before the RCD trips. A 300 mA device never replaces the 30 mA personal protection.
  • Fire protection in fire-risk locations (timber, straw, dust).
  • Agricultural and horticultural installations per IEC 60364‑7‑705.
  • Upstream protection of long cable runs with high leakage current.
  • Selective (short-time delayed) type S version for grading.

How do you combine 30 mA and 300 mA?

Many installations use both values in a graded arrangement. An upstream selective 300 mA RCD of type S protects the main distribution against fire, while downstream 30 mA RCDs secure the individual final circuits for personal protection. The type S trips with a short delay, so a fault first clears the nearer 30 mA device and only the affected circuit switches off.

This selectivity per IEC 60364‑5‑53 keeps a single fault from shutting down the whole installation. Equally important is choosing the RCD type (A, F, B) to match the fault-current waveform of the connected loads, for example with frequency inverters or charging equipment.

Enclosure build

How to arrange RCDs, circuit breakers and distribution to standard.

Read the guide

Frequently asked questions

Is a 300 mA RCD enough for personal protection?

No. 300 mA only protects against fires from insulation faults. For personal protection, IEC 60364‑4‑41 requires an RCD with IΔn ≤ 30 mA, because higher currents can be life-threatening.

Why exactly 30 mA and not 50 mA?

From around 30 mA a current can trigger ventricular fibrillation if it persists. A 30 mA RCD disconnects fast enough that this dangerous limit is not reached, making it the recognised threshold for personal protection.

Can I combine 30 mA and 300 mA RCDs?

Yes, this is common practice. A selective 300 mA RCD of type S protects the main distribution against fire, while downstream 30 mA RCDs protect the final circuits. The time delay ensures selectivity.

When do even 10 mA make sense?

In especially hazardous areas such as medical locations or for very sensitive applications, a 10 mA RCD adds further protection. For standard sockets, 30 mA is sufficient.

Looking for the right residual current device?

We supply RCDs in 30 mA for personal protection and 300 mA for fire protection, including selective type S and types A, F and B.

Standard-tested

RCDs per IEC 60364-4-41 and 60364-5-53.

Personal protection

30 mA devices for safe final circuits.

Fire protection

300 mA devices for installations and buildings.

Expert advice

Our technical editors help with the sizing.

More guides