Standard valves Namur (VDE,VDI 3845)
Standard control valves
Festo standard valves to Namur (VDE/VDI 3845) are solenoid valves that plug directly onto the control ports of pneumatic rotary actuators via the Namur interface, generating the pilot pressure signal there. The NVF3-MOH-5/2-K-1/4-EX is a 5/2-way valve with Ex approval, suitable for safe operation in potentially explosive atmospheres. The G 1/4 control port concept allows mounting without additional pipework directly on the actuator.
The Namur interface to VDE/VDI 3845 defines the hole pitch and control port for direct mounting of solenoid valves on rotary actuators. Namur-interface valves are cross-manufacturer interchangeable, provided the port size (G 1/4 or G 1/2) matches. Ex valves of the NVF3-MOH-...-EX series are approved for zone II (gas groups IIA, IIB, IIC) and are used where electrical control devices must meet the safety requirements of the process plant.
Typical applications: Process plants in the chemical and petrochemical industry with ATEX requirements, butterfly and ball valve actuators in Ex zones, tank farm and pipe manifold automation, and refinery and gas installations where solenoid valves must be mounted directly on rotary actuators.