Mipolam Biocontrol EL5

Floor coverings

Mipolam Biocontrol EL5 combines a conductive floor covering with a full cleanroom qualification. The homogeneous vinyl is 2 mm thick, supplied as a 200 cm x 20 m roll, and reaches a resistance Rg between 104 and 106 Ω to EN 1081. It also carries test values that purely technical ESD coverings do not provide: particle emission class ISO 5 to ISO 14644-1, cleanability with 98.8 % reduction of particle contamination, and resistance to gaseous hydrogen peroxide.

Conductive, 104 to 106 Ω to EN 1081 and EN 14041 - additionally tested to IEC 61340-4-1, IEC 61340-4-5 and ANSI/ESD STM 7.1 and 97.1
Cleanroom class ISO 5 to ISO 14644-1 - particle emission measured by the Fraunhofer method, anion and ammonium emission not measurable at 23 °C
H₂O₂ resistant, suitable for GMP - no change after the BIOQUELL procedure, microbial adhesion class A to ISO 14698-1
Cleanability 98.8 % - reduction of particle contamination to VDI 2083 part 9.1 and ISO 14644-9
📦 Four colours, UPEC U4 P3 E2/3 C2 - Light Fog, Volcano, Horizon and Medium Fog, LRV from 7 to 55.2
Roll 200 cm x 20 m, 2985 g/m², Evercare™ - homogeneous type I build, antibacterial to ISO 22196 and antiviral to ISO 21702

PropertyStandardValue
Overall thicknessEN ISO 243462,0 mm
Weight per areaEN ISO 239972985 g/m²
Roll widthEN ISO 24341200 cm
Roll lengthEN ISO 2434120 m
Installation method-fully bonded
Binder contentEN ISO 10581Typ I
Product standard-EN ISO 10581
European classificationEN ISO 1087434 - 43
Reaction to fireEN 13501-1Bfl-s1
Electrical resistanceEN 1081 / EN 14041104 < Rg < 106
Electrical resistanceIEC 61340-4-1 / IEC 61340-5-1Rgp < 109
Electrical resistanceANSI/ESD STM 97.1 / S20.20106 < Rg < 109
Body voltage generationEN 1815< 2 kV
Body voltage generationIEC 61340-4-5 / ANSI/ESD STM 97.2< 100 V
ESD protectionIEC 61340-5-1 / ANSI/ESD S20.20compliant
Slip resistanceDIN 51130R9
Impact sound reductionEN ISO 717-25 dB
Dimensional stabilityEN ISO 23999≤ 0,4 %
Residual indentationEN ISO 24343-1≤ 0,1 mm
Castor chair suitabilityISO 4918yes, type W
Thermal conductivityEN ISO 104560,25 W/(m·K)
Colour fastness to lightEN ISO 105-B02≥ 6
Surface treatment-Evercare™
Antibacterial activityISO 22196> 99 % growth inhibition
Antiviral activityISO 2170299.7 % after 2 h, 99.9 % after 5 h
Chemical resistanceEN ISO 26987very good resistance
Particle emissionISO 14644-1ISO 5
Air cleanliness classISO 14644-8ACCm/AMCm < -7,7
Cleanability classVDI 2083 Bl. 9.1 / ISO 14644-998.8 % reduction of particle contamination
Microbial adhesionISO 14698-1 / GMPclass A
Resistance to gaseous H₂O₂ISO 14644-4 / GMPno change
UPEC classification-U4 P3 E2/3 C2
TVOC after 28 daysISO 16000-6< 10 µg/m³
Certificate-FloorScore™
CE markingEN 14041compliant

Complete values including test conditions are given in the Mipolam Biocontrol EL5 data sheet available for download in this category. Resistance values are measured before installation.

ColourArticle numberNCSLRV
2001 Light Fog8665-20012002-B50G55,2
2002 Volcano8665-20027010-R90B7
2004 Horizon8665-20042040-R90B33,4
2006 Medium Fog8665-20063005-R80B40,6

The LRV values (light reflectance value) support lighting and contrast planning, the NCS notation helps to match wall and furniture colours.

Typical applications: cleanrooms in pharmaceutical and biotechnology production under GMP requirements, sterile filling and API manufacturing, medical device cleanrooms, laboratories using H₂O₂ decontamination, and operating theatres and procedure rooms that also require a conductive floor.

Position within the range: Mipolam Biocontrol ESD+ shares the cleanroom background but keeps body voltage below 35 V rather than 100 V and is aimed at the most demanding EPA areas. Without cleanroom requirements, Mipolam EL5 offers the same resistance range.

Price and availability on request. We calculate quantity, waste allowance, welding rod and accessories for your project: send an enquiry.