How to size a wiring duct by fill ratio and heat

A wiring duct is not packed to the brim - it is sized by a permissible fill ratio and the heat it must dissipate. This guide shows how to work out cross section, a 60 to 70 percent fill ratio and spare capacity for later additions.

5 minStand: 2026-07Geprüft: Technical editors
View wiring ducts
60-70 %
permissible fill ratio
≥ 30 %
spare for later additions
+10-20 °C
rise in a packed duct
Slots
improve heat dissipation
Inhalt
  1. Fill ratio and reserve
  2. Heat and current rating
  3. Choosing cross section
  4. Frequently asked questions

What does permissible fill ratio mean?

The fill ratio describes how much of the free duct cross section is taken up by cables. In practice a wiring duct is filled to only 60 to 70 percent, so cables can be laid in, the cover closes securely and heat can escape.

An overfilled duct pushes the cover open, pinches conductors and traps loss heat. The remaining 30 to 40 percent is not waste - it is working room for installation and reserve for future additions.

Rule of thumb: divide the sum of the cable outer cross sections by the clear duct cross section. If the result stays below 0.7, the duct is correctly sized.
  • Use the cable outer diameter, not the copper cross section, for the calculation.
  • Round bundles never pack to 100 percent - air gaps always remain.
  • Plan at least 30 percent spare capacity for extensions.
  • The cover must close without force and without conductors bulging out.
Control panel layout

How to plan ducts, DIN rails and terminals to standard.

Read the guide

Why is heat dissipation decisive?

Every current-carrying conductor generates loss heat. When many cables lie tightly bundled in the duct they can no longer cool one another - the current rating drops and must be reduced by a grouping factor.

Under IEC 60364‑5‑52 and DIN VDE 0298‑4, bundled cables call for derating factors: from around nine grouped conductors the factor is about 0.7, meaning the permissible current rating falls to roughly 70 percent. A packed duct can raise conductor temperature by 10 to 20 kelvin.

Slotted duct walls (finger or slotted ducts) improve convection and let warm air escape. In hot enclosures that helps heat dissipation more than closed solid-wall ducts.

How to choose cross section and duct type

Wiring ducts come in stepped widths and heights, typically from 25 x 25 mm to 100 x 100 mm. To select one, add the outer cross sections of all cables and divide by a target fill ratio of about 0.65.

  • Route power and control cables in separate ducts to reduce interference coupling.
  • Choose a duct height so conductors do not protrude past the fingers.
  • With heavy loading go wider and shallower rather than narrow and tall - better cooling.
  • Use covers, dividers and branches from the same duct system.
  • Select halogen-free, flame-retardant PVC or PC/ABS to meet the fire requirement.
Worked example: 20 cables at 5 mm outer diameter give about 20 x 19.6 mm² = 393 mm² plus air. At a 65 percent target you need at least about 600 to 700 mm² clear cross section - a 25 x 40 mm duct fits with reserve.

Frequently asked questions

How full can a wiring duct be?

In practice 60 to 70 percent of the clear cross section. Beyond that the cover no longer closes cleanly, heat dissipation suffers and there is no reserve left for extensions.

Why must I derate current for grouping?

Tightly bundled conductors can no longer cool one another. IEC 60364‑5‑52 and DIN VDE 0298‑4 therefore apply a derating factor that cuts the permissible load to 70 percent or less for many cables.

Slotted or solid-wall duct?

Slotted ducts improve convection and heat dissipation and make it easier to break out conductors. Solid-wall ducts look tidier and are fine at low occupancy.

How much spare capacity should I plan?

At least 30 percent free cross section, so later extensions are possible without swapping the duct and adding new conductors is not a struggle.

Looking for the right wiring duct?

We supply slotted and solid-wall ducts in all common grid sizes including covers and accessories - halogen-free and flame-retardant.

All grid sizes

From 25 x 25 to 100 x 100 mm in stock.

Good heat dissipation

Slotted ducts for loaded enclosures.

Flame-retardant

Halogen-free materials for fire safety.

Expert advice

We help with cross section and fill ratio.

More guides